Product Details
Cast Steel Ball Float Steam Trap (FT14-Thread)
The FT14-T is ball float steam trap having stainless steel working internals and integral automatic air venting facility. The FT14-T can be maintained without disturbing the pipework.
Available types
FT14 (R-L) Horizontal connections with flow from right to left
FT14 (L-R) Horizontal connections with flow from left to right
Sizes and pipe connections
½", ¾" and 1" screwed BSP or NPT.
Limiting Condition |
Body design conditions |
PN16 |
PMA Maximum allowable pressure |
16 bar g @ 100°C |
TMA Maximum allowable temperature |
250°C @ 13 bar g |
Minimum allowable temperature |
-10°C |
PMO Maximum operating pressure for saturated steam service |
14 bar g |
TMO Maximum operating temperature |
250°C @ 13 bar g |
Minimum operating temperature |
0°C |
PMX Maximum differential pressure |
FT14-4.5 |
4.5 bar |
FT14-10 |
10 bar |
FT14-14 |
14 bar |
Designed for a maximum cold hydraulic test pressure of 24 bar g |
Material: Body:A216 WCB
Bonnet:A216 WCB
Seat:Stainless Steel
Ball Float and Lever:Stainless Steel
Capacities
Capacities shown above are based on condensate at saturation temperature. When discharging sub-cooled condensate the air vent provides extra capacity. Under start-up conditions when the condensate is cold the internal thermostatic air vent will be open and provides additional capacity to the main valve. On 4.5 bar units this will provide a minimum of 50% increased capacity above the hot condensate figures shown. On 10 and 14 bar units this will be a minimum increase of 100% on the published capacity. The above table gives the minimum additional cold water capacities from the air vent.